MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Cartop needs to be cleaned
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm does not work on auxiliary power. Re-inspection required
|
12/13/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency light in car does not work on auxiliary power. Re-inspection required
|
12/13/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.5 - Access to Hoistway
|
8.6.4.14 Hoistway Access Switches
|
x
|
|
Hoistway access switches at top and bottom floors do not work to allow workers to safely access car top and pit, needs repaired. Re-inspection required
|
|
A17.1-2016 : Elevators
|
4.5 - Access to Hoistway
|
8.6.4.14 Hoistway Access Switches
|
x
|
|
Hoistway access switches at top and bottom floors do not work to allow workers to safely access cartop and pit, repair same. Re-inspection required
|
12/13/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Provide & install test tag permanently marked with test data on all appropriate equipment. Re-inspection required
|
12/13/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.7.2 Periodic Test Record (Test Tags)
|
|
|
Provide and install test tags permanently marked with test data on all appropriate equipment
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.28 - Counterweight and counterweight buffer
|
2.21
|
|
|
There is a bottom guide roller on the counterweight that is cracked and shall be replaced.
|
|