Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage There is no fireman’s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required. 10/14/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Phase I fire service key switch bezel at main landing is unreadable, replace same 10/14/2025
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage There is no fireman's emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required 10/14/2025
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage There is no fireman's emergency service phase I instruction adjacent to the keyed switch at the primary egress floor, as required 10/14/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Phase I fire service key switch bezel at main landing is unreadable, needs to be replaced 10/14/2025
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage There is no fireman’s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required. 10/14/2025
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage There is no fireman’s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Counterweight runby is 1 inch. Minimum runby is 6 inches. Hoist ropes need to be shortened to achieve at least 6 inches runby, needs repaired. Re-inspection required
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone in car shall work. Re-inspection required 4/22/2025
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x x Overspeed governor rope is damaged, replace same. Re-check pull out / pull thru when rope is replaced. Red-tagged. Re-inspection required 1/18/2025
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Car safeties were damaged during testing, repair or replace and re-inspect with full load, at contract speed. Red-tagged, Re-inspection required 1/18/2025
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)6 x x Overspeed governor speed switch is set too close to jaw tripping speed. Adjust and re-inspect. Red-tagged, re-inspection required 1/18/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone in car shall work. Re-inspection required 1/18/2025