MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A copy of the MCP needs to be kept in the elevator machine room for each unit.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.11 Runby (Re-Inspection)
|
x
|
|
Counterweight runby is 1 inch, minimum is 6 inches. Hoist ropes need to be shortened to achieve at least 6 inches, needs repaired and Re-inspection required
|
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
x
|
Overspeed governor rope is damaged, replace same. Red-tagged, removed from service. Re-inspection required
|
1/18/2025
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Repair machine room lighting to provide at least 10 fc illumination at floor by controller
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace damaged / missing electrical fitting on door operator motor
|
10/14/2025
|
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)5
|
x
|
x
|
Safety operated switch broke during testing. Red-tagged, needs to be replaced. Re-inspection required
|
1/18/2025
|