Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Provide & install test tag permanently marked with test data on all appropriate equipment. Re-inspection required 10/14/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone in car is not working on auxiliary power. Re-inspection required 10/14/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Door closers at top and bottom floors are not working 10/14/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self closing and locking 10/14/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self closing and locking
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Repair existing lighting in machine room and provide for additional lighting if needed to provide required 10 fc minimum illumination at floor in front of controller
MO Minimum : Elevators (H) - Machine Rooms (H)8 Need to install cover on 4x4 electrical box in corner by disconnect switches and enclose all exposed wiring.
MO Minimum : Elevators (I) - Pits (I)1 Pit has had 9 inches of oil / water, has possible black mold. Pit needs to be cleaned ad mold abated. Recommend after cleaning remove any rust from equipment and apply rust inhibitor to prevent any further damage to equipment
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)4 Provide & install crosshead data plate with manufacturer name, date of installation, speed & rated capacity stamped on it. 10/14/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Repair / replace ventilation fan in car 10/14/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace leaking Victaulic fittings as needed in pit and machine room
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x x OSV failed testing, needs repaired. Red-tagged and removed from service. Re-inspection required