Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts The position indicating or “PI” device in the car was not operational on the day of inspection. Repair “PI” device to indicate the position of the elevator car. 10/14/2025
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 The belts on the hydraulic pump motor are loose and slip tension under higher pressure. Tighten belts for a smooth operation of pump to motor. 10/14/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Provide & install test tag permanently marked with test data on all appropriate equipment. Re-inspection required 10/14/2025
MO Minimum : Elevators (I) - Pits (I)1 Pit had 9 inches of water/oil mixture, has possible black mold. Abate mold and clean pit. Recommend removing any rust on equipment after cleaning and applying inhibitor to prevent additional damage.
MO Minimum : Elevators (I) - Pits (I)8 Cover shall be re-installed over sump pump hole