Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)6 Has active Floating platform switch required to be made inactive. Code 210.12 1/5/2021
MO Minimum : Elevators (H) - Machine Rooms (H)1 Install Proper machine room door. 2.1 - 101.3c(2) 1/5/2021
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Install proper machine room lighting. 2.3 -101.5a 1/5/2021
MO Minimum : Elevators (F) - Electrical Switches (F)9 Mainline Disconnect to be replaced and moved to allow proper access 1/5/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No DO NOT USE ELEVATOR IN CASE OF FIRE 1/5/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No records 1/5/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams No wiring diagrams (1926 Otis elevator) 1/5/2021
MO Minimum : Elevators (H) - Machine Rooms (H)1 Provide proper access to roof to provide proper access to elevator machine room. 2.1- Rule 101.3b (1) 1/6/2021
MO Minimum : Elevators (F) - Electrical Switches (F)9 Remove existing machine room motor disconnect and replace with proper disconnect. NEC Code 620.51 1/5/2021