MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
The car remote inspection station does not operate as designed and would not operate properly. The device shall be repaired or replaced to operate as designed.
|
9/14/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
A permanent lighting fixture shall be provided in all pits to provide an illumination of not less than five (5) foot-candles at the pit floor. The fixture switch shall be provided and accessible from the pit access door.
|
9/14/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
|
|
Needs alarm bell installed
|
9/14/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
The lighting in the elevator machine room is not sufficient. The lighting shall not be less than (10) foot candles at the floor level.
|
|
MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)5
|
|
|
The in car lighting only has one fixture operational, the second fixture shall be repaired to operate.
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
Fire extinguisher needs to be serviced.
|
12/1/2018
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
The lighting in the elevator machine room is not sufficient. The lighting shall not be less than (10) foot candles at the floor level.
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The emergency alarm bell did not operate, repair alarm bell.
|
5/4/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The testing has not been completed on the elevator at this time. The safeties shall be set before the inspection is completed.
|
2/23/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required.
|
8/31/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The elevator alarm bell inside the elevator is not working. Check and repair the alarm bell for proper operation and passenger safety. Reinspection required.
|
8/31/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The emergency alarm bell did not operate, repair alarm bell.
|
2/23/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The emergency lighting in the car failed to operate, repair/replacement is required.
|
2/23/2023
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)1
|
x
|
x
|
The stop switch in the car failed to operate, repair/replacement and reinspection is required.
|
2/23/2023
|