Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power 8/26/2026
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 Yes No Machine Space shall have at least one(1) GFCI outlet. Currently available outlet 8/26/2026
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 2.29.1 Yes No Machinery, controllers, governors, disconnects shall be numbered conspicuously. 8/26/2026
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.18.3 Yes No Governor - Speed governors shall have their means of speed adjustment sealed after test. 8/26/2026
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 2.19.2 Yes No Unintended Motion shall be a maximum of 48" 8/26/2026
A17.1-2016 : Elevators 3.27 - Crosshead data plate 8.7.2.17.3 Decrease in Rated Speed Yes No Suspension and Governor ropes shall have proper data tag(s) See also 2.18.5.3 & Rule211.2b 8/26/2026
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.8 Switch Keys Yes No Fire Service Phase 1 switch at level 446 not working 8/26/2026
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters’ Emergency Operation: Operating Procedures (Signage) Yes No Fire Alarm Initiating Devices at 446 shall recall to 465(main). FAID at 465 shall recall to 446(ALT). FAID at 430 shall have solid hat, not flashing. 8/26/2026
conversion conversion n/a No No Missing code data plate 8/3/2018
conversion conversion n/a No No Repair broken control room door (will not close) 8/3/2018
conversion conversion n/a No No Lights inside cab cahll be guarded. 8/3/2018
conversion conversion conversion - reinspect Yes No Repair Door Restrictor (Reinspect) 10/9/2018
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Clean machine room of non-elevator equipment. 12/1/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Fire extinguisher needs to be serviced. 12/1/2018
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No H.1 - The drop ceiling in the machine room is degrading due to water seepage and shall be repaired. 9/14/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that either the device is not hooked up to a back-up power device or the back-up power device as failed. Repair for proper operation. Reinspection required. 5/4/2023