MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
Yes
|
No
|
When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that either the device is not hooked up to a back-up power device or the back-up power device as failed. Repair for proper operation. Reinspection required.
|
5/4/2023
|
|
A17.1-2016 : Elevators
|
2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection
|
2.19.2
|
Yes
|
No
|
Unintended Motion shall be a maximum of 48"
|
8/26/2026
|
|
A17.1-2016 : Elevators
|
3.27 - Crosshead data plate
|
8.7.2.17.3 Decrease in Rated Speed
|
Yes
|
No
|
Suspension and Governor ropes shall have proper data tag(s) See also 2.18.5.3 & Rule211.2b
|
8/26/2026
|
|
conversion
|
conversion
|
conversion - reinspect
|
Yes
|
No
|
Repair Door Restrictor (Reinspect)
|
10/9/2018
|
|
conversion
|
conversion
|
n/a
|
No
|
No
|
Repair broken control room door (will not close)
|
8/3/2018
|
|
conversion
|
conversion
|
n/a
|
No
|
No
|
Missing code data plate
|
8/3/2018
|
|
A17.1-2016 : Elevators
|
2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches
|
2.29.1
|
Yes
|
No
|
Machinery, controllers, governors, disconnects shall be numbered conspicuously.
|
8/26/2026
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
Yes
|
No
|
Machine Space shall have at least one(1) GFCI outlet. Currently available outlet
|
8/26/2026
|
|
conversion
|
conversion
|
n/a
|
No
|
No
|
Lights inside cab cahll be guarded.
|
8/3/2018
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
No
|
No
|
H.1 - The drop ceiling in the machine room is degrading due to water seepage and shall be repaired.
|
9/14/2021
|
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.18.3
|
Yes
|
No
|
Governor - Speed governors shall have their means of speed adjustment sealed after test.
|
8/26/2026
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.8 Switch Keys
|
Yes
|
No
|
Fire Service Phase 1 switch at level 446 not working
|
8/26/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
No
|
No
|
Fire extinguisher needs to be serviced.
|
12/1/2018
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.7 Firefighters’ Emergency Operation: Operating Procedures (Signage)
|
Yes
|
No
|
Fire Alarm Initiating Devices at 446 shall recall to 465(main). FAID at 465 shall recall to 446(ALT). FAID at 430 shall have solid hat, not flashing.
|
8/26/2026
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
Yes
|
No
|
Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power
|
8/26/2026
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
No
|
No
|
Clean machine room of non-elevator equipment.
|
12/1/2018
|