Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency phone not working. Alarm bell ok. 11/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)1 x Large plumbing pipe in access path. Variance is requested. 3/31/2023
MO Minimum : Elevators (H) - Machine Rooms (H)1 Existing pipe prevents unobstructed path to machine room
MO Minimum : Elevators (H) - Machine Rooms (H)1 Need unobstructed path to machine room. Existing large plumbing pipe may need variance.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door must be self-closing and self-locking
MO Minimum : Elevators (H) - Machine Rooms (H)2 Needs non combustible separation of machine room
MO Minimum : Elevators (H) - Machine Rooms (H)2 x Machine room door must be self-closing and self-locking. 3/31/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 x Wall separating machine room is combustible material. Not fire rated 3/31/2023
MO Minimum : Elevators (I) - Pits (I)1 Wooden platform in pit not needed for elevator operation
MO Minimum : Elevators (I) - Pits (I)1 x A wooden partial platform between pit floor and buffers attached to the front of hoistway wall is not needed for elevator operation. 3/31/2023
MO Minimum : Elevators (I) - Pits (I)1 Wooden platform in pit
MO Minimum : Elevators (I) - Pits (I)5 Pit access ladder needed to be installed
MO Minimum : Elevators (I) - Pits (I)5 Needs pit ladder
MO Minimum : Elevators (I) - Pits (I)5 Ladder needed in pit
MO Minimum : Elevators (I) - Pits (I)5 x Ladder needed in pit 3/31/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) x Light needed in pit 3/31/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Light needed in pit
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Needs pit light
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light mounted but not wired yet Need to complete
MO Minimum : Elevators (I) - Pits (I)7 x Additional stop switch needed in deep pit 3/31/2023
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.2-211.8 x x Mod in 2004, Phase I 2.27.3.1.6(a) violation recalled to alternate floor. Phase 11. 2.27.3.3.1 Phase ii operation not functional Red Tagged Car. 2/24/2023