Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers A17.1 2004 2.2.2.6 Sumps and sump pumps in pits, where provided, shall be covered. The cover shall be secured and level with the pit floor. PUMPS ARE LOCATED ABOVE FLOOR, NOT ALLOWING PIT TO FULLY DRAIN CAUSING DAMAGE TO PIT EQUIPMENT. (CHECK INTEGRITY OF PIT CHANNELS & BUFFER STANDS BEFORE CAT 5 FULL LOAD TESTING IN 2025) 3/13/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x A17.1 2004 ITEM 1.6 CAR EMERGENCY SIGNAL 2.27.1 REPROGRAM EMERGENCY PHONES TO TK OR TO PBHA ANSWERING SERVICE 6/22/2023
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) A17.1 – 2016 8.6.1.4.1 On-Site Maintenance Records: 8.6.1.4.1(c)(2) A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation. 11/1/2021