MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
REPLACE BAD HOIST ROPES
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
PHONE IS NOT WORKING
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Door does not open when door open button is pushed while elevator is on fire service phase 2 operation.
|
9/16/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Remove firefighter call cancel button from car operating panel. Firefighter operation on this elevator was not designed for call cancel feature.
|
8/31/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state operating certificate in machine room.
|
9/20/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Test and log firefighter operation monthly
|
9/20/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Elevator cab lighting is insufficient, less than 5 foot candles of illumination.
|
9/20/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Braille plates next to car button #1, and on floor 1 entrance frame, need to have a star on them to designate 1 as the main fire landing. Remove star on LL car button, and on floor LL entrance frame.
|
9/20/2022
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Exposed 110 volt wiring on door operator needs to be enclosed in metal raceway.
|
9/21/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Insufficient car lighting inside the elevator. Car lighting needs to be a minimum of 5 foot candles of illumination.
|
9/21/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Post firefighter operating instructions inside the elevator that comply with fire service features that the elevator was constructed to meet. Existing signage is incorrect.
|
9/21/2022
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Install cover over exposed 110 volt wiring on car door control box.
|
9/21/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate inside machine room
|
9/21/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Test and log firefighter operation monthly
|
9/21/2022
|