Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Car lighting is less than 5 ft candles of illumination. Need to provide adequate lighting inside the elevator. 3/16/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Elevator cab lighting is insufficient, less than 5 foot candles of illumination. 9/20/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room access door needs to be self-locking 9/20/2022
MO Minimum : Elevators (H) - Machine Rooms (H)8 THE 110VAC BREAKER LABELED ELEVATOR #1 DID NOT REMOVE POWER. WE COULD NOT TEST EMERGENCY LIGHT AND ALARM
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x REPLACE BAD HOIST ROPES
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed in machine room 9/20/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate in the machine room. 9/20/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Remove firefighter call cancel button from car operating panel. Firefighter operation on this elevator was not designed for call cancel feature. 8/31/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Braille plates next to car button #1, and on floor 1 entrance frame need a star on them to designate 1 as the main fire landing. Remove star on LL car button, and floor LL entrance frame. 9/20/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Need to test firefighters operation monthly and keep written record log inside machine room. 3/16/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Test and log firefighter operation monthly 9/20/2022