Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams The wiring diagram must be provided in the machine room so it is accessible to the inspector and the technician. 11/4/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods There shall be maintenance records in the elevator machine room or accessible to the inspector. Shall consist of maintenance task such as callbacks, examinations, test, adjustments, and replacements. 11/4/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Repair inoperative pressure switch. 11/4/2020
MO Minimum : Elevators (R) - Power Operated Special Purpose Elevators (R)6 x Doors shall be equipped with interlocks. Elevator red tagged.
MO Minimum : Elevators (R) - Power Operated Special Purpose Elevators (R)6 x The current hoistway door interlock does not prevent the door from being opened when the car is away from the landing. The door shall be provided with approved interlocks. 10/16/2020
conversion conversion n/a Post current Mo operating certificate in machine room 6/4/2019
conversion conversion n/a Car hits condult for room lighting when test is performed need to move condult 6/4/2019
conversion conversion n/a need maintenance records on site 6/4/2019
conversion conversion n/a Lighting in car must be functional 6/4/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The Current operating certificate shall be posted in the machine room in a non combustible frame 11/4/2020