MO Minimum : Elevators
|
(R) - Power Operated Special Purpose Elevators
|
(R)9
|
x
|
x
|
Gates must have interlocks and be at least 7" high at each landing. Red tagged elevator.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair inoperative emergency phone.
|
4/30/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current certificate in machine room.
|
10/15/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)2
|
|
|
Secure cab panel to platform.
|
10/15/2020
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
|
|
Replace missing gate latches at 1st and 2nd landings.
|
10/15/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Repair gate restrictor for proper operation.
|
10/15/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The Current operating certificate shall be posted in the machine room in a non combustible frame
|
10/15/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
There shall be maintenance records in the elevator machine room or accessible to the inspector. Shall consist of maintenance task such as callbacks, examinations, test, adjustments, and replacements
|
10/15/2020
|
conversion
|
conversion
|
n/a
|
|
|
Emergency phone not working
|
10/15/2020
|
conversion
|
conversion
|
n/a
|
|
|
Post MO operating certificate in machine room
|
10/15/2020
|
conversion
|
conversion
|
n/a
|
|
|
Need maintenance control program
|
10/15/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Provide protection for cab lighting.
|
10/15/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
Emergency phone line must call and be received by a 24 hour service line.
|
10/16/2020
|
MO Minimum : Elevators
|
(R) - Power Operated Special Purpose Elevators
|
(R)6
|
|
x
|
The current hoistway door interlock does not prevent the door from being opened when the car is away from the landing. The door shall be provided with approved interlocks.
|
10/16/2020
|
MO Minimum : Elevators
|
(R) - Power Operated Special Purpose Elevators
|
(R)9
|
x
|
x
|
The hoistway gate must be at least 7 feet high at each landing sill.
|
10/16/2020
|