Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)3 Replace missing gate latches at 1st and 2nd landings. 10/15/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Repair inoperative emergency phone. 4/30/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)2 Secure cab panel to platform. 10/15/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Provide protection for cab lighting. 10/15/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x Emergency phone line must call and be received by a 24 hour service line. 10/16/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Repair gate restrictor for proper operation. 10/15/2020
MO Minimum : Elevators (R) - Power Operated Special Purpose Elevators (R)6 x The current hoistway door interlock does not prevent the door from being opened when the car is away from the landing. The door shall be provided with approved interlocks. 10/16/2020
MO Minimum : Elevators (R) - Power Operated Special Purpose Elevators (R)9 x x The hoistway gate must be at least 7 feet high at each landing sill. 10/16/2020
MO Minimum : Elevators (R) - Power Operated Special Purpose Elevators (R)9 x x Gates must have interlocks and be at least 7" high at each landing. Red tagged elevator.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The Current operating certificate shall be posted in the machine room in a non combustible frame 10/15/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current certificate in machine room. 10/15/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods There shall be maintenance records in the elevator machine room or accessible to the inspector. Shall consist of maintenance task such as callbacks, examinations, test, adjustments, and replacements 10/15/2020
conversion conversion n/a Emergency phone not working 10/15/2020
conversion conversion n/a Post MO operating certificate in machine room 10/15/2020
conversion conversion n/a Need maintenance control program 10/15/2020