Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Install sleaves on Florescent light bulbs in car 10/28/2019
conversion conversion n/a Provide missing access panel to machine space 10/28/2019
conversion conversion n/a Post current state certificate in machine space 10/28/2019
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)5 x x Platform safety pan is broken off and there is no way to actuate safety switch. 10/4/2019
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Platform safeties would not set. Red tagged. 10/4/2019
MO Minimum : Elevators (R) - Power Operated Special Purpose Elevators (R)6 x Hoistway doors shall comply with A17.1 1978 Part XV
MO Minimum : Elevators (R) - Power Operated Special Purpose Elevators (R)9 x A door or gate shall guard the entire entrance, at least 7' high of metal construction and provided with interlocks.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams Controller access cover needs to be non-combustible material. 6/3/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current operating certificate. 6/3/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Car safety pan shall be non-combustible material. 6/3/2020