| MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)9 | x | x | Doors shall be equipped with interlocks. Red tagged elevator. |  | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and  Wiring Diagrams |  |  | Electrical diagrams shall be provided on site. | 11/4/2020 | 
                
                    | MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)6 |  | x | The current hoistway door interlock does not prevent the door from being opened when the car is away from the landing. The door shall be provided with approved interlocks. | 10/16/2020 | 
                
                    | MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate |  |  | The Current operating certificate shall be posted in the machine room in a non combustible frame | 7/24/2020 | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and  Wiring Diagrams |  |  | The electrical prints for the elevator must be accessible to the inspector and the technician in the machine room. | 7/24/2020 | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | x |  | The emergency phone line must call and be received by a 24 hour service line. | 10/16/2020 | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods |  |  | There shall be maintenance records in the elevator machine room or accessible to the inspector. Shall consist of maintenance task such as callbacks, examinations, test, adjustments, and replacements. | 7/24/2020 |