Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (R) - Power Operated Special Purpose Elevators (R)9 x x Doors shall be equipped with interlocks. Red tagged elevator.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams Electrical diagrams shall be provided on site. 11/4/2020
MO Minimum : Elevators (R) - Power Operated Special Purpose Elevators (R)6 x The current hoistway door interlock does not prevent the door from being opened when the car is away from the landing. The door shall be provided with approved interlocks. 10/16/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The Current operating certificate shall be posted in the machine room in a non combustible frame 7/24/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams The electrical prints for the elevator must be accessible to the inspector and the technician in the machine room. 7/24/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The emergency phone line must call and be received by a 24 hour service line. 10/16/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods There shall be maintenance records in the elevator machine room or accessible to the inspector. Shall consist of maintenance task such as callbacks, examinations, test, adjustments, and replacements. 7/24/2020