MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Pit wall penetration ( sump and sprinkler lines) must be fire proof caulked/filled
|
9/20/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
B(11)/1.6.1/8.11.2.1.1(f) : 2-way communication device shall work and give proper location. Water damage. REINSPECTION REQUIRED
|
10/26/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)6
|
|
|
B(6) / 112.5 Detector edge not working. Water damage.
|
9/20/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
B(11)/1.6.1/8.11.2.1.1(f) : 2-way communication device shall work and give proper location. Water damage. REINSPECTION REQUIRED
|
10/26/2021
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1002.2f
|
x
|
|
Top of Hoistway heat detectors need to be moved to within 2’ .
|
10/26/2021
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1002.2f
|
x
|
|
Top of Hoistway heat detectors need to be moved to within 2’ .
|
10/26/2021
|