MO Minimum : Elevators
|
(I) - Pits
|
(I)7
|
|
|
I(7). Pit Stop Switch shall work.
|
1/12/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Phase 2 Switch Halo to be replaced( unreadable and not proper color)
|
1/23/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
6.2.2(a)(4) Detector edge shall be bypassed on fire service.
|
1/25/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
x
|
|
1.7.1 : Car Gate switch shall not register “closed” at greater than 2” open.
|
1/22/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
1.7.1 : Car Gate switch shall not register “closed” at greater than 2” open.
|
1/22/2021
|