MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
: Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame.
|
11/4/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
MCP shall be kept in equipment room
|
11/4/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Entrance to equipment shall be kept free of clutter( vacuum cleaners, mop bucket, 2wheel dolly observed).
|
11/4/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Machine Room Fire Extinguisher shall have current annual test tag. (Expired April 2016)
|
11/4/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Machine room lighting needs to be repaired, 1 or more bulbs not working. Bulbs will be guarded against breakage.
|
1/23/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm shall work with power loss. (REINSPECTION within 30 days)
|
10/2/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm shall work with power loss. (REINSPECTION within 30 days)
|
12/4/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm shall work with power loss. (REINSPECTION within 30 days)
|
12/4/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
G(1)/8.6.4.15/1.5.1(b) : Emergency/auxiliary lighting shall work with power loss. (REINSPECTION REQUIRED)
|
10/26/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
G(1)/8.6.4.15/1.5.1(b) : Emergency/auxiliary lighting shall work with power loss. (REINSPECTION REQUIRED)
|
10/26/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)12 (Door open zones)
|
x
|
|
B(12)/112.2a Car doors shall not open automatically until within 6" of the floor level. (Door Zone. Unit automatically opens door when door circuit is opened/clipped ).
|
1/25/2023
|