MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
2019/2020 : 2-way communication device shall work and give proper location (REINSPECTION within 30 days)
|
1/22/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
2019/2020 : 2-way communication device shall work and give proper location (REINSPECTION within 30 days)
|
1/22/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide operational telephone in elevator cab
|
7/6/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
telephone line is disconnected
|
9/24/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
8.6.4.13 Adjust upthrusts for proper clearance (including but not limited to:8, 9,16,18)
|
10/31/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
2.4.2.1 suspension ropes need to be shortened
|
10/22/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Suspension rope shackles while have “anti-rotation”device installed, broken
|
9/30/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)6
|
|
|
H(6) Mainline disconnects, controllers, machines, and governors shall be numbered to correspond to each unit.
|
10/22/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
H(8). Multiple 4x4 electrical box in machine room needs to have wiring inside box and cover installed.
|
10/22/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
H(8). 4x4 electrical box in machine room needs to have wiring inside box and cover installed. ( phone connect box and Mach room lighting)
|
9/6/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Provide operational pit light
|
7/18/2023
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Hoist ropes has reduced diameter and shall be replaced within 30days.
|
10/31/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Machine Room Fire Extinguisher shall have current monthly/annual test tag. Expired 2019
|
9/30/2021
|