MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm bell shall work with power loss.
|
10/14/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
Car Door restrictor shall work, Front and Rear
|
10/14/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
Emergency/auxiliary lighting shall work with power loss
|
10/14/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm shall work with power loss. (REINSPECTION within 30 days)
|
2/24/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm shall work with power loss. (REINSPECTION within 30 days)
|
2/24/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.8 - Door closing force
|
8.11.2.1.1(h)
|
x
|
|
REDUCE DOOR PRESSURE TO 30# MAX
|
2/24/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.8 - Door closing force
|
8.11.2.1.1(h)
|
x
|
|
REDUCE DOOR PRESSURE TO 30# MAX
|
2/24/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.7 Firefighters' Emergency Operation: Operating Procedures
|
|
|
Install compliant fire service Phase 1 instructions at main recall landing
|
6/22/2022
|