Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Car Door restrictor shall work. (REINSPECTION > 5/28/22) 6/2/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate in machine room 9/5/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x emergency light not working 12/3/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x OSV shall have current testing tag. 5yr weight test required for 2022, then every 5 years starting 2026.. (Noted on 2021 inspection form). TEST TO BE COMPLETED WITHIN 90 DAYS 6/2/2023
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept dry. Buffer stands to be cleaned off, and painted for rust protection. Investigate water source and correct. 10/17/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x Pit shall be kept dry. Pit channels and pipe stand shall be replaced due to severe water damage. (See photos) REINSPECT 7/28/22 6/2/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x telephone not working 12/3/2019