Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | x | 2" of Counterweight Runby with Elevator at the top terminal landing. 6" is the minimum Runby requirement. Hoist rope need to be shortened. | ||
MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | ropes rusty / ridge | 3/5/2024 |