MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Must make Car Door Restrictor Operable. 1.18
|
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
ropes rusty / ridge
|
3/5/2024
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.2 Replacement of Suspension Means (Re-Inspection)
|
x
|
|
Must replace Hoist ropes due to exceeding No of allowable Breaks in a lay. (Found 12 breaks in a lay)
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.11 Runby (Re-Inspection)
|
x
|
|
2" of Counterweight Runby with Elevator at the top terminal landing. 6" is the minimum Runby requirement. Hoist rope need to be shortened.
|
3/5/2025
|