Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x 2" of Counterweight Runby with Elevator at the top terminal landing. 6" is the minimum Runby requirement. Hoist rope need to be shortened.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x ropes rusty / ridge 3/5/2024