MO Minimum : Elevators
|
(A) - Hoistways
|
(A)1
|
|
|
Replace the missing cotter pit on the door closer rod, 2nd floor.
|
7/1/2020
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Remove abandoned electrical conduit at the rear of the hoistway.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Provide a current tested fire extinguisher in the machine room.
|
7/1/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room door shall be self-locking.
|
7/1/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
x
|
|
The machine room door shall be self-locking.
|
7/10/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Pipes conveying liquid, gas, or vapor that cross overhead of elevator equipment or come in close proximity of the equipment shall be guarded or guttered. This is in reference to the pipe behind and over the elevator controller.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Pipes conveying liquid, gas, or vapor that cross overhead of elevator equipment or come in close proximity of the equipment shall be guarded or guttered. This is in reference to the pipe behind and over the elevator controller. Repeat violation.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
The machine room shall be cleaned.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
All non-elevator related equipment or materials shall be removed from the machine room.
|
7/1/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Lighting in the machine room shall be not less than 10 foot-candles at floor level.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Lighting in the machine room shall be not less than 10 foot candles at floor level. Repeat violation.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. Repeat violation.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean the pit of oil.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
x
|
Fluids are leaking from the jack head/plunger gripper area. Repair as needed.
|
7/1/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove fluids from the pit.
|
7/1/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean the pit of oil. Repeat violation.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
x
|
|
Remove the fluids from the pit. The pit shall be kept dry.
|
7/10/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
A permanent lighting fixture shall provide an illumination of not less than five foot-candles at the pit floor. Repeat violation.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
A permanent lighting fixture shall provide an illumination of not less than five foot-candles at the pit floor.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Provide a permanent, non-combustible pit sump pump cover capable of supporting at least 200 lbs.
|
7/1/2020
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)2
|
|
x
|
Observed a relief pressure of 700 psi. This pressure exceeds last years pressure of 400. Repair and retest the relief pressure.
|
7/1/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room. No MCP or documentation present in room. Repeat violation.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.5 Code Data Plate
|
|
|
Install a code data plate. It shall read "Missouri Minimum". Repeat violation.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.5 Code Data Plate
|
|
|
Install a code data plate. It shall read "Missouri Minimum".
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
x
|
|
A current tested fire extinguisher is required in the elevator machine room.
|
7/10/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
The fire extinguisher is out of date.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. Expired 2019. Repeat violation
|
|