MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit steel very rusty -- replace--due to bad flaking
|
6/25/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Newly installed dryer vent, PVC pipe runs across machine room, remove or get variance
|
6/25/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
No emergency telephone
|
3/13/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
mechanical edge doesnt stall door on ph 1 activation its over ridden
|
3/11/2025
|