Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 8.11.2.3.2 | x | 8.11.2.3.2(b) Governor Rope pull thru and pull out shall be tested. Dynamometer on site failed. | 5/22/2024 | |
conversion | conversion | n/a | Bottom floor door frame loose | 7/24/2018 | ||
conversion | conversion | n/a | No "c" measurement--shorten ropes | 7/24/2018 | ||
conversion | conversion | n/a | Machine room lights not working | 7/24/2018 |