Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.1(h) Call Cancel Button (Re-Inspection) x call cancel on phase 2 doesnt work 3/11/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.2 x 2.4.2.1 Counterweight Runby minimum is 6 inches current Runby is 2 inches. Ropes require shortening. 2/20/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.5 Phase 1 Visual Signal (Re-Inspection) x Phase I Recall has no visual or audible signal. Must reinspect. 2/20/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x No alarm bell 5/22/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 8.11.2.1.2(d) Radio equipment installed in machine room-non elevator. remove or request variance 5/7/2019