Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No B(11)/1.6.1 : Alarm shall work with power loss. (REINSPECTION within 30 days) 12/23/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No B(11)/1.6.1 : Alarm shall work with power loss. (REINSPECTION within 30 days) 12/23/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No G/2.7.1/8.6.1.6.5: Machine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag. 4lb installed, should be 5-10lbs ABC 9/15/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No G(1).3.26.10 Battery Lowering shall work. Repair or replace. 9/15/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Machine Room Fire Extinguisher shall have current monthly/annual test tag. 11/17/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Battery lowering device shall work with power loss. 11/17/2020
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Phase 2 shall work, "Hold" does not work. 12/23/2020
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Phase 2 shall work, "Hold" does not work. 12/23/2020
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Phase 2 switch not working properly. 8/10/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Provide current state operating certificate 8/14/2023