A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
|
|
1.5 Emergency light needs battery
|
8/29/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Machine Room Fire Extinguisher shall have current monthly/annual test tag.
|
11/17/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Severe water damage to pit channels - shall be replaced within 30days (REINSPECTION WITHIN 30 days)
|
11/17/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be kept dry. Water/sludge in pit again. See pics. Pit steel recently replaced but water intrusion persists
|
9/15/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly. (Provided by Elev Co)
|
9/15/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
B(11)/1.6.1/ : 2-way communication device shall work(with and w/o main power) and give proper location. Unresponsive (REINSPECTION 14days to REDTAG
|
2/7/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Provide current state operating certificate
|
8/14/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be kept dry
|
8/14/2023
|