Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Machine Room Fire Extinguisher shall have current monthly/annual test tag. 11/17/2020
MO Minimum : Elevators (H) - Machine Rooms (H)7 No No Machine Room outlet shall be replaced with GFI protected outlet. 1/4/2022
MO Minimum : Elevators (A) - Hoistways (A)16 No No Reinstall missing cartop limit switch cover (switch tree) 1/4/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Replace missing Hall Braille floor numbers @1, 2 1/4/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Replace missing “in case of fire” signage (all floors) 1/4/2022
MO Minimum : Elevators (H) - Machine Rooms (H)7 No No 2021&2022 Violation: H(7) Machine Room outlet shall be replaced with GFI protected outlet 10/15/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No 8.6.1.6.7 Replace missing "in case of fire" signage (all floors) 10/15/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No G(1)/A17.1-2016:8.6.1.2.1(a)/2.40 Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly 8/18/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Provide current state operating certificate 8/14/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No 8.6.4.15 EMERGENCY LIGHTING SHALL WORK (Only 1 bulb works) 7/21/2023