MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
No
|
No
|
Drive sheave liner is worn out on the middle cable, needs replacement. Recommend replacing all 3 sheave liners
|
5/6/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
No
|
No
|
Drive sheave liner is worn out on middle cable, needs replacement. Recommend doing all 3 sheave liners
|
5/6/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
No
|
No
|
Drive sheave liner is worn out on the middle cable, needs replaced. Recommend replacing all 3 sheave liners
|
5/6/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
No
|
No
|
There is no fireman’s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required.
|
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
No
|
No
|
The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor.
|
|
|
A17.1-2016 : Elevators
|
3.2 - Car top light and outlet
|
2.14.7.1.4
|
No
|
No
|
The car top inspection light/fixture did not operate. Repair light/fixture for proper operation and illumination for maintenance/emergency personnel.
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Inspection incomplete. Need to perform the following tests: car & counterweight buffers need testing, 125% brake test, full load test of safeties, adjust governor and spin test for proper speeds. Re-inspection required
|
4/10/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
Yes
|
The SOS switch on the safety plank would not reset after testing the safeties, elevator is shout off until SOS switch is repaired. This test is incomplete, car & counterweight oil buffers need to be tested. Red-tagged, Re-inspection required
|
4/11/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Need to perform testing of car & counterweight buffers to complete Cat 5 inspection. Re-inspection required
|
12/15/2025
|