MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Testing for the 5 year is incomplete. Complete the following test to finish the 5 year test: 125% load brake test, and setting of the safeties to get a slide measurement.
|
4/10/2026
|
|
A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.6.3.2 (Re-Inspection)
|
Yes
|
No
|
The counterweight is touching the oil buffer when the elevator travels to the top floor. The hoist ropes shall be shortened or spacing device removed to provide a minimum runby of 6 inches. Reinspection required within 30 days.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
No
|
No
|
There is no fireman’s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required.
|
|