Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a No No Make adjustments so car can reach its up final limit. 6/4/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No The elevator hoistway door at the 1st floor landing shall be adjusted to be self closing/self locking,
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No The pit light fixture failed to illuminate in the pit. Repair pit light fixtures to provide lighting of not less than five (5) foot candles at the pit floor for maintenance and emergency personnel.