A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
|
9/4/2026
|
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
206.7
|
Yes
|
No
|
Replace Hoist Ropes. Reinspection not required.
|
2/11/2019
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Test incomplete, need to test 125% brake test, full load safety test, car & counterweight buffer test. Re-inspection required
|
2/4/2023
|