Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing has not been completed on this unit at this time, the elevator shall be repaired and a reinspection on the car safeties shall be performed before the inspection is completed. 9/9/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.29 - Car and counterweight safeties Table 2.17.3 x x The elevator car safeties failed to set within the parameters set forth by the current adopted code. The elevator is removed from service until the car safeties are repaired or replaced. 9/9/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.33 - Compensating ropes and chains 2.21.4 Compensating ropes are undersized. Replace by 3/11/20 2/20/2020