Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The testing has not been completed on the elevator at this time. The emergency lighting and alarm bell shall be tested before the inspection is completed.
MO Minimum : Elevators (I) - Pits (I)1 No No Clean oil out of pit. 6/11/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No The elevator car top escape hatch is unopenable due to water swelling the wood. The escape hatch shall be repaired to open as required.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No There is no fire extinguisher in the machine room, as required. Provide an ABC type extinguisher of proper size for the room.
conversion conversion conversion - reinspect Yes No Refasten jack to car platen plate connection 7/12/2018