A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
No
|
No
|
Pit light is not working.
|
2/21/2020
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
No
|
No
|
Sump pump not working.
|
2/21/2020
|
|
conversion
|
conversion
|
n/a
|
No
|
No
|
Repair bottom right guide shoe.
|
6/4/2019
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
No
|
No
|
Clean oil out of pit.
|
6/11/2021
|
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
No
|
No
|
Jack head need to be repacked.
|
6/11/2021
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
No
|
No
|
Elevator machine room shall not be used for storage of non elevator equipment
|
4/28/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
No
|
No
|
There is no fire extinguisher in the machine room, as required. Provide an ABC type extinguisher of proper size for the room.
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
The testing has not been completed on the elevator at this time. The emergency lighting and alarm bell shall be tested before the inspection is completed.
|
|