Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The testing has not been completed on the elevator at this time. The emergency lighting and alarm bell shall be tested before the inspection is completed.
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Elevator machine room shall not be used for storage of non elevator equipment 4/28/2022
MO Minimum : Elevators (I) - Pits (I)1 No No Clean oil out of pit. 6/11/2021
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 No No Jack head need to be repacked. 6/11/2021
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No Pit light is not working. 2/21/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No Sump pump not working. 2/21/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No There is no fire extinguisher in the machine room, as required. Provide an ABC type extinguisher of proper size for the room.
conversion conversion n/a No No Repair bottom right guide shoe. 6/4/2019