Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 No No Clean oil out of pit. 6/11/2021
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Elevator machine room shall not be used for storage of non elevator equipment 4/28/2022
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 No No Jack head need to be repacked. 6/11/2021
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No Pit light is not working. 2/21/2020
conversion conversion n/a No No Repair bottom right guide shoe. 6/4/2019
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No Sump pump not working. 2/21/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The testing has not been completed on the elevator at this time. The emergency lighting and alarm bell shall be tested before the inspection is completed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No There is no fire extinguisher in the machine room, as required. Provide an ABC type extinguisher of proper size for the room.