Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Emergency alarm bell does not function. 7/30/2018
MO Minimum : Elevators (H) - Machine Rooms (H)4 Hydraulic oil on machine room floor due to leaking control valve. 4/4/2019
MO Minimum : Elevators (I) - Pits (I)1 Pit floor has oil accumalation. Oil source is from leak in machine room. 4/4/2019
MO Minimum : Elevators (I) - Pits (I)1 Need to remove standing hydrauluc oil from elevator pit. Pits need to be kept clean and dry. 5/6/2020
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Post firefighter operating instructions next to hall fire keyswitch
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Remove scavenger pump from pit. Cylinder drain line needs to drain into pit collection container of no more than 5 gallon capacity
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal x No visual signal during fire recall operation 4/12/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Test and log firefighter operation monthly
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Post firefighter operating instructions next to hall fire keyswitch
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Post In Case of Fire Do Not Use Elevator signage next to lobby corridor call station.
MO Minimum : Elevators (A) - Hoistways (A)16 110 volt wiring to 3rd and 4th floor stopping switches in the hoistway needs to be in metal conduit
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Clean elevator car top.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No maintenance records on site.
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal x No visual signal during fire recall operation. 12/16/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Remove scavenger pump from pit.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit Remove standing water/oil mixture from pit