MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
110 volt wiring to 3rd and 4th floor stopping switches in the hoistway needs to be in metal conduit
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Hydraulic oil on machine room floor due to leaking control valve.
|
4/4/2019
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit floor has oil accumalation. Oil source is from leak in machine room.
|
4/4/2019
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Need to remove standing hydrauluc oil from elevator pit. Pits need to be kept clean and dry.
|
5/6/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
x
|
|
No visual signal during fire recall operation
|
4/12/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
x
|
|
No visual signal during fire recall operation.
|
12/16/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Post firefighter operating instructions next to hall fire keyswitch
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Post firefighter operating instructions next to hall fire keyswitch
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
No maintenance records on site.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Post In Case of Fire Do Not Use Elevator signage next to lobby corridor call station.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Test and log firefighter operation monthly
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.7 Cleaning of Hoistway and Pit
|
|
|
Remove standing water/oil mixture from pit
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Clean elevator car top.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Remove scavenger pump from pit.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Remove scavenger pump from pit. Cylinder drain line needs to drain into pit collection container of no more than 5 gallon capacity
|
|
conversion
|
conversion
|
n/a
|
|
|
Emergency alarm bell does not function.
|
7/30/2018
|