MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
The lighting in the elevator machine room above the drive machine is not sufficient. The lighting shall not be less than (10) foot candles at the floor level.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
The fireman’s emergency service phase II instruction signage adjacent to the keyed switch in the car is worn off and unreadable. Replace signage as required.
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
This elevator has a backup emergency power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Cables are roughing and need replacing. Cables on are contract to be changed Jan 2019.
|
1/16/2019
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Replace governor rope. 2.13.2.1 (a)
|
6/10/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Phase 2 signage needs to be replaced inside of car. 6.1.2.(g)(1) No need to red tag or reinspect.
|
6/20/2020
|
conversion
|
conversion
|
n/a
|
|
|
Repair machine room lights
|
6/20/2020
|
conversion
|
conversion
|
n/a
|
|
|
Replace hoist (supension) rope within 30 days.
|
6/20/2020
|