Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Repair machine room lights 6/20/2020
conversion conversion n/a Replace hoist (supension) rope within 30 days. 6/20/2020
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Phase 2 signage needs to be replaced inside of car. 6.1.2.(g)(1) No need to red tag or reinspect. 6/20/2020
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The lighting in the elevator machine room above the drive machine is not sufficient. The lighting shall not be less than (10) foot candles at the floor level.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The fireman’s emergency service phase II instruction signage adjacent to the keyed switch in the car is worn off and unreadable. Replace signage as required.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Cables are roughing and need replacing. Cables on are contract to be changed Jan 2019. 1/16/2019
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Replace governor rope. 2.13.2.1 (a) 6/10/2020