Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 4/16/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 2.20 The suspension ropes shall be tagged as specified by code. 4/16/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.20 - Governor rope 2.18.5 The governor rope shall be tagged as specified by code. 4/26/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) All machine room wiring shall be enclosed. (Note: Knockout holes in wireway shall be covered, and the missing box cover shall be installed). 4/26/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 4/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams Need to replace or repair the drive on the controller