Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No "in case of fire sign" adjacent to top floor hall button 2/1/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door must be self closing & self locking 2/1/2022
MO Minimum : Elevators (I) - Pits (I)1 Remove water in pit 2/1/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.2 x Counterweight runby is below minimum. Hoist ropes need to be shortened to get proper runby within 60 days. Re-inspection required 3/15/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.8 Switch Keys (Re-Inspection) x All fire recall switches shall match. Re-inspection required 12/19/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) x All fire recall switches shall match. Re-inspection required