ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.8 Switch Keys (Re-Inspection)
|
x
|
|
All fire recall switches shall match. Re-inspection required
|
12/19/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6 Fire Fighters Operation (Re-Inspection)
|
x
|
|
All fire recall switches shall match. Re-inspection required
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
2.4.2
|
x
|
|
Counterweight runby is below minimum. Hoist ropes need to be shortened to get proper runby within 60 days. Re-inspection required
|
3/15/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
Keys that operate Fire Service should be the same for all elevators in the same building. Did NOT red-tag unit.
|
3/19/2019
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door must be self closing & self locking
|
2/1/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
No "in case of fire sign" adjacent to top floor hall button
|
2/1/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove water in pit
|
2/1/2022
|